QUICK START - Socomec

ATyS Mounting of Auxiliary Contacts
Applicable to ATyS r, d, t, g, p models ≤ 1600A
DANGER
• This equipment must be installed and serviced only by qualified electrical
personnel.
• Turn off all power supplying this equipment before working on or inside
equipment.
• Always use a properly rated voltage sensing device to confirm power is off.
• Replace all devices, doors, and covers before turning on power to this
equipment.
• Maintain electrical clearances between cable and live parts.
Failure to follow these instructions will result in death or serious injury.
STEP 1
http://www.socomec.
com/en/changeover
EN
QUICK
T
STAR
FR
ES
www.socomec.com
DANGER
• L’installation et l’entretien de cet appareil doit être effectués que par du
personnel qualifié.
• Coupez l’alimentation de cet appareil avant d’y travailler.
• Utilisez toujours un dispositif de détection d’absence de tension (VAT) pour
confirmer que le produit est hors tension.
• Replacez tous les dispositifs, les portes et les couvercles avant de mettre
cet appareil sous tension.
• Vérifier les distances d’isolement entre les câbles, et également entre les
câbles et toutes parties métalliques.
Si ces précautions ne sont pas respectées, cela pourrait entraîner de graves
blessures, une électrisation, voir même une électrocution.
543 309 A - 10/14
PELIGRO
•Solamente el personal de mantenimiento eléctrico especializado debera
instalar y prestar servicios de mantenimiento a este equipo.
• Desenergice el equipo antes de realizar cualquier trabajo en él.
• Siempre utilice un dispositivo detector de tensión adecuado para confirmar
la desenergización del equipo.
• Vuelva a colocar todos los dispositivos, las puertas y las cubiertas antes de
energizar este equipo.
• Mantenga un espacio adecuado para la instalación eléctrica entre el cable y
las piezas energizadas.
El incumplimiento de estas precauciones podrá causar la muerte o lesiones
serias.
REMOVAL / DÉMONTAGE / REMOCIÓN
2a
3
1
ATyS r
2
4
4a
2b
3
ATyS r, d, t, g, p
1
ATyS d, t, g, p
Removing the motorisation module from the Power Section
4b
125 -> 630 A
1
2
5
800 -> 1600 A
STEP 2
ASSEMBLING / MONTAGE / MONTAJE
Assembling the auxilliary contacts on the Power Section
1
82 84 81
Ref. 1599 0532
(800-1600A)
Pos II
Ref. 1599 0502
(125-630A)
Pos
II
Pos
II
Pos II
3
2
Pos I
92 94 91 (fast-on)
(1)
Pos II
2
Ref. 4109 0021
When mounting one auxiliary contact on
position I or II, use the short screws provided.
When mounting two auxiliary contacts on
position I or II, use the long screws provided.
(1)
Pos
I
Pos
I
4.4 lb-in
0,5 Nm
Pozidriv n°1
Pos I
Recto-verso / papier blanc offset 80g/m2 / noir et blanc / format ouvert : 210x297mm / format plié : 105x148,5mm - Non contractual document. Subject to change without notice.
STEP 2a
ASSEMBLY DETAILS FOR 125 -> 630 A / MONTAGE / MONTAJE
2x
max
Ref. 1599 0502
max. 2 Aux Contact
per position
Pos I
81
Pos II
84
82
92
91
94
81 82 84 91 92 94
125 -> 630 A
Flying lead
and connectors
1
2
Pos. = Pos.
STEP 2b
3a
125 -> 630 A = 3 Nm
ASSEMBLY DETAILS FOR 800 -> 1600 A
1
2
3
4
Ref. 1599 0532 max. 2
Aux Contact per position
5
0.5 Nm
6
7
10
11
8
Pos. = Pos.
II
Pos
Pos
Attn: drill right through before
inserting screws
II
0.5 Nm
9
Pos I
Pos II
800 -> 1600 A - 5 Nm
81
Pos
82
84
91
92
94
I
2x
max
81 82 84 91 92 94
800 -> 1600 A - Fixed lead and connectors